Présentation du produit
Intelligent instrument calibrator for PT CT error and impedance admittance test.It meets the requirements of JJG313-94 current transformer verification regulation and JJG314-94 voltage transformer verification regulation.
Product Characteristics
1、Intelligent transformer calibrator adopts 320 240 lattice liquid crystal, with large visual range and long life backlight, convenient to use
2、Chinese operation interface, beautiful interface
3、The percentage difference Angle difference is displayed in large font, which is convenient for users to observe
4、The intelligent transformer calibrator produced by our company fully meets the requirements of jjg314-1993 and jjg314-1994, and it can be sampled automatically
5、Automatically judge polarity error, change ratio error
6、The upper computer software has the open function of virtual instrument
7、Completely solve the s-level measurement problem
8、Automatic range switching
9、The perfect combination of advanced and unique circuit and DSP technology can completely remove the problem of the circuit instability
10、power dissipation:<15VA(No micro printer);<25VA(microprinter)
11、Harmonic suppression ratio:>40db
12、boundary dimension(Band dimensions):260×350×150mm3
13、weight:6kg
paramètres techniques
| Environnement d'exploitation de l'équipement | temperature:5℃~40℃ | relative humidity:<80%(25℃) |
| altitude:<2500m | ||
| mains frequency:50Hz±0.5Hz | mains input:220V±5V | |
| plage de mesure | cophase component(%):0.0001~200.0 | distinguishability:0.0001 |
| orthogonal component(part):0.001~700.0 | distinguishability:0.001 | |
| impedance(Ω):0.0001~20.0 | distinguishability:0.0001 | |
| admittance(ms):0.0001~20.0 | distinguishability:0.0001 | |
| erreur intrinsèque | composant cophase | ΔX=±(X×2%+Y×2%)±Dx(Level 1 is optional) |
| composante orthogonale | ΔY=±(X×2%+Y×2%)±Dy(Level 1 is optional) | |
| "X"、"Y"——Display value of instrument | ||
| "Dx,Dy"——Display value of instrument | ||
| Dx=2,Dy=5 | ||
| indicateur d'appel | PETS2 (le niveau 1 est facultatif) | |
| Plage de travail | électricité | (1%~149%)In (In =5A) |
| (5%~149%)In (In =1A) | ||
| tension | (5%~149%)Un (Un =100V,150V,100V/) | |
| (5%~149%)Un (Un =100V/3) | ||
| charge de travail | électricité | TO to TX<0.12Ω cosΦ=1 |
| tension | a to x<0.25VA (100V) | |
| Indication d'erreur de polarité | Lorsque le courant de fonctionnement (tension) atteint plus de 5 % du courant nominal (tension) et que l'erreur dépasse 180 %, il doit y avoir une indication de polarité. | |
| Remarque : s'il est supérieur à 10 % du courant de fonctionnement nominal (tension), il n'y a toujours pas d'indication de polarité correcte, indiquant un défaut. Veuillez ne pas augmenter le courant (tension) pour éviter de brûler l'instrument. | ||
| Indication d'erreur de rapport variable | Lorsque le courant de fonctionnement (tension) atteint plus de 5 % du courant nominal (tension) et que l'erreur dépasse 30 % mais est inférieure à 180 %, l'indication d'erreur du rapport variable doit être donnée. | |
| Test d'isolement et de tension et instructions | terminalTX( | |
| The power socket can withstand the housing1.5kV,1minwithstand voltage | ||