qiao@hvtest.cc15871365102
  • What is the BDV test for oil?

    LeTesteur d'huile BDV under Wuhan UHV can help many power workers conduct various power tests more conveniently.


    HTY_0006-2

    What is the BDV Test for Oil?

    The BDV Test refers to the Breakdown Voltage Test.

    BDV stands for Breakdown Voltage.


    Purpose of the Test

    It is used to evaluate the electrical insulation strength of insulating oils (e.g., transformer oil, switchgear oil, cable oil). Simply put, it measures the oil’s ability to resist electrical breakdown (formation of a conductive path) under an electric field.


    Test Principle

    1.Sample Preparation: An oil sample is poured into a standardized test cell.

    2.Electrode Setup: Two electrodes (typically spherical or spherical-plane) are positioned at a precise standard gap (usually 2.5 mm).

    3.Voltage Application: An increasing AC voltage (typically 50/60 Hz) is applied between the electrodes.

    4.Breakdown Observation: Voltage rises until a sudden breakdown occurs (visible spark/arc), causing a surge in current.

    5.Result Recording: The voltage (in kilovolts, kV) at the moment of breakdown is recorded as the Breakdown Voltage (BDV).


    Why is the BDV Test Critical?

    Key Metric: BDV is one of the most direct and important indicators of an oil’s insulation performance.

    Pollution Sensitivity: BDV values are highly sensitive to contaminants:

    Moisture: Trace water significantly reduces BDV by forming conductive "bridges."

    Solid Particles: Dust, fibers, or metal particles create conductive paths.

    Dissolved Gases: Bubbles from gases are prone to breakdown.

    Oxidation Products/Sludge: Aging byproducts (acids, sludge) degrade BDV.

    Oil Condition Assessment: BDV reveals whether oil is contaminated, wet, or aged, determining its fitness for insulation duties.

    Maintenance Decisions: BDV results dictate if oil requires filtration, drying, reclamation, or replacement. For example, if transformer oil BDV drops below a safety threshold (e.g., 30 kV), action is mandatory.

    New Oil Validation: New insulating oil must pass BDV testing before use (typical new oil BDV >60 kV).


    Summary

    The BDV test is a critical electrical performance assessment for insulating oils. By measuring the voltage required to electrically break down the oil under controlled conditions, it directly evaluates the oil’s insulation strength. BDV levels primarily reflect contaminants like moisture and particles, making it the foremost indicator for determining oil quality, operational safety, and maintenance needs. It is indispensable in power equipment (e.g., transformers, switchgear) maintenance and oil management


    Vous pourriez aussi aimer

    • Avez-vous des questions!

      N'HÉSITEZ PAS À NOUS CONTACTER À TOUT MOMENT
      Contactez-nous
    • Rendez nous visite

      Bâtiment 6, parc industriel optique-mécanique d'Optics Valley, 84 Gaoxin 5 Road,
      Zone de développement de nouvelles technologies d'East Lake, ville de Wuhan, province du Hubei, Chine

    • Envoyez-nous un email

      qiao@hvtest.cc

    • Appelez-nous

      +86-15871365102