qiao@hvtest.cc15871365102
  • Testeur de rapport de transformation triphasé UHV-331

    Le testeur de rapport de transformation du transformateur UHV-331 est principalement utilisé pour mesurer le rapport de transformation et le groupe du transformateur. Il est applicable aux transformateurs connectés en type Z et au traitement de données flexible, y compris la récupération, l'impression, le transfert sur un disque U, la suppression et le téléchargement sur un ordinateur PC. pour tester.

    Product Details of UHV-331 Three Phase TTR Transformer Turns Ratio Tester


    Transformer Turn Ratio Tester

    Présentation du produit

    Transformer Turns Ratio Tester is specially designed for three-phase transformer in power system, especially for transformer of type Z winding and other transformers whose zero-load current is relatively high. The tester has wide testing range, fast testing speed, favorable repeatability, flexible data processing, convenient connection, complete protection, easy learningand convenient operation. 


    Paramètres techniques


    Plage de test du rapport de transformation0.8~10000
    Gamme de tests de groupe0~11
    Ransformation ratio testing accuracyclass 0.1 (HV:0.8~200)
    class 0.2 (HV:200~1000)
    class 0.5 (HV:1000~10000)
    class 0.2 (LV:0.8~100)
    Résolution du rapport de transformation0.0001
    Entrée de puissance220 V ± 10 %, 50 Hz ± 1 Hz
    La température de service-20℃~40℃
    Humidité relative≤85 %, pas de condensation
    Taille globale de la machine hôte325mm×280mm×190mm
    Poids de la machine hôte6,9 kg


    Product Characteristics

    1、Suitable for transformers with Z-type connections.

    2、Offers two output voltage options, ideal for transformers with high zero-sequence current.

    3、Wide measurement range with a maximum transformation ratio of up to 10,000.

    4、Automatic tap position calculation.

    5、Fast operation: completes three-phase measurement in just 18 seconds.

    6、Excellent repeatability with consistent and stable results.

    7、Can automatically store up to 99 sets of test data.

    8、Flexible data handling: supports retrieval, printing, export to USB drive, deletion, and upload to PC.

    9、Includes transformer short-circuit protection and inter-turn short-circuit protection; fault information is displayed on the LCD screen in case of a short circuit.

    10、Compatible with PC software for full-process testing control and data management.

    11、Comes with a detailed operation manual for user convenience.

    12、Compact design, slightly larger than an A4 sheet of paper.

    13、Lightweight, weighing only 6.9 kg.








    Vous pourriez aussi aimer

    • Avez-vous des questions!

      N'HÉSITEZ PAS À NOUS CONTACTER À TOUT MOMENT
      Contactez-nous
    • Rendez nous visite

      Bâtiment 6, parc industriel optique-mécanique d'Optics Valley, 84 Gaoxin 5 Road,
      Zone de développement de nouvelles technologies d'East Lake, ville de Wuhan, province du Hubei, Chine

    • Envoyez-nous un email

      qiao@hvtest.cc

    • Appelez-nous

      +86-15871365102